3.6. CURRENT 35 - 110 kV TRANSFORMERS
Type |
Rated voltage, kV |
Rated primary current, A |
Rated secondary current, A |
Number of secondary windings |
Rated power of secondary windings in accuracy classes, VA | |||||
0,2S | 0,2 | 0,5S | 0,5 | 5Р | 10Р | |||||
ТФМ-35-II-У1 |
35 |
15; 30; 50; 75; 150 |
1; 5 |
3 |
20 |
20 |
20 | 20 | - | 20 |
100; 150; 200; 300; 400; 600; 1200 |
30 |
30 |
20 |
20 |
||||||
750; 1500 | ||||||||||
500; 1000; 2000 | ||||||||||
3000 | ||||||||||
ТФМ-35-II-1-У1 |
35 |
600; 1200 |
1; 5 |
3 |
from 10 to 40 |
from 10 to 40 |
||||
750; 1500 | ||||||||||
800 | ||||||||||
1000; 2000 | ||||||||||
3000 | ||||||||||
4000 | ||||||||||
ТФМ-110-II-У1 |
110 |
100; 150; 200; 300; 400; 600; 1200 |
1; 5 |
4 |
20 |
30 |
30 |
30 |
30 |
30 |
750; 1500 |
40 |
40 |
||||||||
500; 1000; 2000 |
||||||||||
ТФМ-110-II-1-У1 |
110 |
100; 150; 200; 300; 400; 600; 1200 |
1; 5 |
5 |
20 |
30 |
30 |
30 |
30 |
30 |
750; 1500 | 40 | 40 | ||||||||
ДТФ-35-У1*) | 35 | 2 х 100 | 2 х 2,5 | 3 | 20 |